SPEED #3 value. See Parameter 3 - SPEED #3 in Section 18.0 - DESCRIPTION OF
PARAMETERS,
ILIMIT CURRENTLIMIT-Therelayenergizeswhenthedriveisoperatingincurrentlimit.
Once the current limit relay is energized, it remains energized for a minimum of
500ms, regardless of whether the drive is still in current limit. At the end of the 500ms
interval, the relay will de-energize if the drive is no longer in current limit. See
Parameter 16 - CURRENT in Section 18.0 - DESCRIPTION OF PARAMETERS.
AUT/MAN AUTO/MANUAL MODE - The relay energizes when the drive is in the
AUTOMATIC mode, and de-energizes in the MANUAL mode. Refer to Section
14.2.5 - SPEED REFERENCE SELECTION.
FLWRPR FOLLOWERPRESENT-Therelayenergizeswhentheanaloginputreferencesignal
atTB-5Bisgreaterthan2mA,andde-energizesifthesignalfallsbelow2mA.
REVERSE TherelayenergizeswhenReversedirectionisselected,andde-energizeswhenForward
direction is selected.
MIN/MAX
ALARM The relay energizes when thefeedbacksignal(in PID mode) or the speed reference
signal(inopen-loopspeedmode)iswithinthelimitssetbyMINALARMandMAX
ALARM(Parameters81and82),andde-energizeswhenthesignalfallsbelowtheMIN
ALARMsettingorexceedstheMAXALARMsetting.
INV
MIN/MAXA INVERSE MIN/MAX ALARM - The relay de-energizes when the feedback signal
(inPIDmode)orthespeedreferencesignal(inopen-loopspeedmode)iswithinthe
limitssetbyMINALARMandMAXALARM(Parameters81and82),andenergizes
whenthe signalfallsbelowtheMINALARMsetting orexceeds theMAXALARM
setting.
MINALARM The relay de-energizes when the feedback signal (in PID mode) or the speed refer-
ence signal (in open-loop speed mode) equals or exceeds the MIN ALARM setting
(Parameter81),andenergizeswhenthesignalfallsbelowtheMINALARMsetting.
INV MIN
ALARM INVERSE MIN ALARM - The relay energizes when the feedback signal (in PID
mode)orthespeedreferencesignal(inopenloop speedmode)equals orexceedsthe
MINALARMsetting(Parameter81),andde-energizeswhenthesignalfallsbelowthe
MIN ALARM setting.
MAXALARM Therelayde-energizeswhenthefeedbacksignal(inPIDmode)orthespeedreference
signal(in open-loopspeed mode)islessthanor equalto theMAX ALARMsetting
(Parameter82),andenergizeswhenthesignalexceedstheMAXALARMsetting.
INV MAX
ALARM INVERSE MAX ALARM - The relay energizes when the feedback signal (in PID
mode)orthespeedreferencesignal(inopen-loopspeedmode)islessthanorequalto
theMAXALARMsetting(Parameter82),andde-energizeswhenthesignalexceedsthe
MAX ALARM setting.
SLEEP TherelayenergizeswhenthedriveisinSLEEPMODE.SeeParameters36-38.
70