Leeson Micro Series Compact Inverters Manual de usuario

Busca en linea o descarga Manual de usuario para Software Leeson Micro Series Compact Inverters. LEESON Micro Series Compact Inverters User Manual [fr] Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir

Indice de contenidos

Pagina 1 - SPEEDMASTER

SPEEDMASTER®Micro Series CompactInverters Installation and Operation ManualA Regal Brand

Pagina 2

84.2 TYPE 1 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac and 60 HP at 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N C P Q S

Pagina 3 - TABLE OF CONTENTS

94.3 WASHGUARD NEMA 4/12, 12, & 4X* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. Slo

Pagina 4 - TABLE OF CONTENTS (cont’d.)

10WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Pagina 5 - IMPORTANT NOTICE

114.4 TYPE 12 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac AND 60 HP AT 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N P Q

Pagina 6 - 1.0 GENERAL

12* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF

Pagina 7

135.0 MICRO SERIES RATINGS115/230 & 230V (SINGLE PHASE) VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (120/240 Vac, 50-60 Hz) (0-230 Vac)

Pagina 8 - 4.0 MICRO SERIES DIMENSIONS

14230 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (200/240 Vac, 50-60 Hz) (0-200/230 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Pagina 9

15460 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (400/480 Vac, 50-60 Hz) (0-400/460 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Pagina 10 - Small holes = 1.13”

16575 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (480/590 Vac, 50-60 Hz) (0-460/575 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Pagina 11 - Others are NEMA 4/12

6.0 THEORY6.1 DESCRIPTION OF AC MOTOR OPERATION ThreephaseACmotorsarecomprisedoftwomajorcomponents,thestatorandtherotor.Thestatoris

Pagina 13

 Ifthefrequencyappliedtothemotorisincreasedwhilethevoltageremainsconstant,torquecapabilitywilldecreaseasspeedincreases.Thiswill

Pagina 14

 “Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed.Also,the horsepower required varies with th

Pagina 15 - 5.0 MICRO SERIES RATINGS

6.2.3 MICRO SERIES INPUTS AND OUTPUTS Thedrivehas two analog inputs (0-10 VDC and 4-20 mA) that can beused for speed reference, PI

Pagina 16 - OTHERS ARE NEMA 1 ENCLOSURE

The following describes the possible relay output settings: NONE This setting disables the relay output. RUN The relay energizes when the dri

Pagina 17

7.0 INSTALLATION DRIVESMUSTNOTBEINSTALLEDWHERESUBJECTEDTO ADVERSE ENVI- RONMENTAL CONDITIONS! DRIVES MUST NOT BE INSTALLED WHERESUBJ

Pagina 18

7.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE Severe damage to the drive can result if it is operated after a long period of storage or inactivity

Pagina 19 - 6.0 THEORY

8.0 INPUT AC REQUIREMENTS Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain

Pagina 20 - % SPEED

9.0 VOLTAGE SELECTION9.1 INPUT VOLTAGE RATINGS 115/230 Volt MICRO Seriesdrivesareratedfor240/120Vac,50-60Hzinput.Thedrivewillfunction

Pagina 21

11.0 MICRO SERIES POWER WIRING DIAGRAM Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.

Pagina 22

12.0 INITIAL POWER UP Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain cha

Pagina 23

TABLE OF CONTENTS1.0 GENERAL ... 4 PRODUCT CHANGES ...

Pagina 24 - 7.0 INSTALLATION

 3. If the motor is rotating in the wrong direction, press the “STOP” key, remove power from the drive, wait three minutes for the

Pagina 25

13.2 MICRO SERIES DISPLAY The following describes the possible display configurations for the SPEEDMASTER MICRO Series drive.13.2.1 MICRO SERIES DI

Pagina 26 - 8.0 INPUT AC REQUIREMENTS

30 The following table shows the possible DRIVE STATUS indications that can appear on the drive display:DRIVE STATUS TABLE DISPLAY DESCRIPTION ST

Pagina 27 - 10.0 POWER WIRING

13.2.2 MICRO SERIES DISPLAY IN RUN MODE WhenthedriveisintheRUNmode,thedefaultdisplaywilllooklikethis: AsintheSTOPmode,theENTER

Pagina 28

3213.2.3 MICRO SERIES DISPLAY IN FAULT MODE When the drive trips on a fault, the display will automatically change to the FAULT display, which indic

Pagina 29 - 12.0 INITIAL POWER UP

33 Thetable belowshowsthe possibleSPEEDREFERENCESOURCEindications fortheauxiliarystatus display:SPEED REFERENCE TABLE DISPLAY DESCRI

Pagina 30 - 13.0 KEYPAD CONTROL

14.0 CONTROL WIRING14.1 GENERAL14.1.1 KEYPAD CONTROL Thedrivecanbecontrolledbythekeypadorbycontroldeviceswiredtotheterminalstrip.T

Pagina 31

14.2 START/STOP AND SPEED CONTROL14.2.1 REMOTE MODE SELECTION The REMOTE mode can be selected by one of two methods: 1. Program Parameter 30 - CO

Pagina 32

14.2.3 ALTERNATE TWO-WIRE START/STOP CONTROL METHOD  This method requires TB-13C to be set for RUN REVERSE, which will disable TB-1 a

Pagina 33

14.2.4 THREE-WIRE START/STOP CONTROL A three-wire start/stop circuit can be accomplished by one of two methods on the MICRO Series drive. Follow the

Pagina 34

TABLE OF CONTENTS (cont’d.)19.0 MICRO SERIES PID SET POINT CONTROL ... 77 FEEDBACK DEVICES . . . . . . . . . . . . . . . .

Pagina 35

14.2.5 SPEED REFERENCE SIGNALS Thedriveallowsforthreeanalogspeedreferenceinputs:aspeedpotentiometer(10,000Ohm),0-10VDC,or 4-20 mA.

Pagina 36 - 14.0 CONTROL WIRING

 JOG TheJOGfunctiononlyworkswhenthedriveisinREMOTEmode,andonlywhenthedriveisinaSTOPcondition.TB-13Bcanbeprogrammedforeith

Pagina 37

15.0 MICRO SERIES CONTROL WIRING DIAGRAMS15.1 MICRO SERIES TERMINAL STRIP Shown below is the terminal strip on the main control board, along with a

Pagina 38

15.2 TWO-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained contact(s

Pagina 39

15.3 THREE-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary contacts(

Pagina 40

15.4 SPEED POT AND PRESET SPEED CONTROL ShownbelowisthewiringdiagramforacontrolschemethatutilizesaspeedpotandPRESETSPEEDSforspeed

Pagina 41

16.0 PROGRAMMING THE MICRO SERIES DRIVE16.1 PROGRAMMING THE PARAMETERS The MICRO Series keypad serves two purposes: operating the drive w

Pagina 42

Once the correct password is entered, the PROGRAM mode will be entered and the first parameter will be displayed, which is Parameter 0 - LINE VOLTS.

Pagina 43

16.2 PARAMETER ACCESS USING SPEED DIAL SPEED DIAL is used to access parameters quickly using the parameter number. Once accessed, the

Pagina 44

4717.0 PARAMETER MENUNOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE

Pagina 45

3IMPORTANT NOTICEThe following , and information is supplied to you for your protection and to provi

Pagina 46 - 20.00 HZ

48NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE3:IFLINEVOLTSIS

Pagina 47

49PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT  43 @TB10A 0.00-360.0HZ(NOTE2) 60.00Hz 44 TB10B O

Pagina 48

50PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT 65 PROGRAM MAINTAIN, RESET 60,   RESET50(NOTE4) RES

Pagina 49 - 17.0 PARAMETER MENU

5118.0 DESCRIPTION OF PARAMETERS 0 LINE VOLTS (LINEVOLTAGE) This parameter calibrates the drive for the correct input voltage, and can be set

Pagina 50

1-4 SPEED #1-#4 (PRESETSPEEDS#1,#2,#3,AND#4) PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact clo

Pagina 51

Example:Thecriticalfrequencyis21Hz,andabandwidthof2Hzisdesired.Therefore,setSKIP#1to20HzandsetSKIPBANDWIDTHto2Hz.Thisr

Pagina 52

54 NOTE 1: 240/120 Vac units have the same limits as 240/200 Vac units. NOTE 2: The parameter value can be set below the minimum value shown, but th

Pagina 53

11 MAX FRQ (MAXIMUMFREQUENCY) Thisparameterdefinestheupperlimitofthedrive’sspeedrange.MAXFRQisusedinconjunctionwithMINFRQ(Par

Pagina 54

14 DYN BRAK (DYNAMICBRAKE) This parameter enables the dynamic braking circuit. Set this parameter to ON only if the optional dyna

Pagina 55

 The“speed-compensated”thermaloverloadcircuitoffersadditionalprotectionfromhighloadconditionsatlowspeeds,wheremotorcoolingisoften

Pagina 56

1.0 GENERAL1.1 This manual covers the LEESON MICRO Series Inverters.1.2 PRODUCT CHANGES LEESON Electric reserves the right to discontinue or

Pagina 57

18 BASE (BASEFREQUENCY) The BASE FREQUENCY determine the V/Hz ratio by setting the frequency at which the drive will output full

Pagina 58

20 AC BOOST (ACBOOST) AC BOOST is similar to FX BOOST, but is only active when the drive is accelerating. During acceleration, theoutputvoltage

Pagina 59 - OUTPUT CURRENT (%)

22 TORQUE (TORQUECURVESELECTION) ThisparameterisusedtoselectwhethertheoutputofthedrivefollowsaconstantorvariableV/Hzcurve.The

Pagina 60

25 START (STARTMODE)  Automaticstartofequipmentmayresultindamagetoequipmentand/orinjurytopersonnel!Automaticstartshouldonlybe

Pagina 61 - OUTPUT VOLTAGE (%)

27 ROTATION (ROTATIONDIRECTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Pagina 62

29 MANUAL (MANUAL) This parameter selects the speed reference source when the drive is set for MANUAL speed control (seeparameter28 - AUTO/MAN

Pagina 63

33 SPEED DP (SPEEDDECIMALPOINT) This parameter is used to move the decimal point location in the speed display. This parameter will not have any

Pagina 64

Example:SLEEP THRESHOLD isset to15Hz andSLEEP DELAYisset to60seconds. Ifthe drive operates below 15Hzfor60 seconds, the dr

Pagina 65

41 AIN FLTR (ANALOGINPUTFILTER) Thisparameteradjuststhefilterontheanaloginputterminals(TB-5AandTB-5B)toreducetheeffectofanyel

Pagina 66

47 TB13A (TB-13AINPUTFUNCTION) This parameter is used to select the function of terminal TB-13A. Closing TB-13A to TB-2 activates the TB-13

Pagina 67

2.0 MICRO SERIES SPECIFICATIONS Storage Temperature -20° to 70° C Ambient Operating Temperature Chassis -10° to 55° C  (With2.5and8kHZcar

Pagina 68

49 TB13C  (TB-13CINPUTFUNCTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Pagina 69

50 TB13D  (TB-13DFUNCTION)  STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaults!The

Pagina 70

SPEED #3 value. See Parameter 3 - SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS, ILIMIT  CURRENTLIMIT-Therelayenergizeswhenthedrive

Pagina 71

71 SPD=0HZ Therelayenergizeswhenthereisnooutputtothemotor,foranyreason,suchas:drive    isinSTOPmode,driveisinRUNmode

Pagina 72

NOTE 2: If a RESET command (Parameter 65 - PROGRAM) is issued through the serial link, this parameter will not default back to

Pagina 73

65 PROGRAM (PROGRAMFACTORYDEFAULTS) STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaul

Pagina 74

70 PID MODE (PIDMODESELECT) This parameter activates the PID function, and selects whether the PID control will be direct or reverse acting.

Pagina 75

NOTE:Ifareverseactingfeedbackdeviceisbeingused,FB@MINshouldbesettothemaximumprocessvariable value, and FB @ MAX should be set to

Pagina 76

relayoropen-collectoroutputwillde-energize,whichopensthestartcontactandstopsthedrive.WhenthesignalisequaltoorgreaterthantheMI

Pagina 77

19.0 MICRO SERIES PID SET POINT CONTROL PID Set point Control allows the MICRO Series Control to maintain a process set point, such as PSI orCFM,w

Pagina 78

64.0 MICRO SERIES DIMENSIONS4.1 TYPE 1 ENCLOSEDWRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ≤ 7

Pagina 79

 Forareverseactingtransducer,setParameter75-FB@MINtothemaximumprocessvariablefeedbackvalue,andsetParameter76-FB@MAXtothe

Pagina 80

eachtype,sothesametypeofsignalcannotbeusedfortransducerfeedbackandsetpointreference.For example,a4-20mAsignalfromatransducer

Pagina 81

When the drive is in PID mode, the DRIVE STATUS portion of the display will indicate actual output frequency(inHertz)insteadofRUN,andtherig

Pagina 82

8120.0 TROUBLESHOOTING The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please con

Pagina 83 - 20.0 TROUBLESHOOTING

82FAULT MESSAGES FAULT DESCRIPTION POSSIBLE CAUSES EXTERNAL Externalfault:TB-13Disopenorclosed ChecksettingofParameter to TB-2, depe

Pagina 84

8321.0 USER SETTING RECORDPARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 0 LINE VOLTS AUTO 1

Pagina 85 - 21.0 USER SETTING RECORD

84PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 20 AC BOOST .0% 21 SLIP CMP .0% 22 TORQUE

Pagina 86

8585PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 42 TB10A OUT NONE 43 @TB10A 60.00Hz 44

Pagina 87

86PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 74 PID FB TB-5A 75 FB @ MIN 0.00% 76 FB

Pagina 88

EC DECLARATION OF CONFORMITYWe,LEESON Electric1051 Cheyenne AvenueGrafton, Wisconsin 53024 U.S.A.declareundersoleresponsibilitythatthefollowing

Pagina 89 - LEESON Electric

7WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Pagina 92 - A Regal Brand

A Regal BrandLEESON ElectricGrafton, Wisconsin 53024 U.S.A.PH: 262-377-8810FAX: 262-377-9025www.leeson.comREGAL BELOIT CANADAMississauga (Toronto), On