SPEEDMASTER®Micro Series CompactInverters Installation and Operation ManualA Regal Brand
84.2 TYPE 1 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac and 60 HP at 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N C P Q S
94.3 WASHGUARD NEMA 4/12, 12, & 4X* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. Slo
10WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q
114.4 TYPE 12 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac AND 60 HP AT 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N P Q
12* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF
135.0 MICRO SERIES RATINGS115/230 & 230V (SINGLE PHASE) VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (120/240 Vac, 50-60 Hz) (0-230 Vac)
14230 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (200/240 Vac, 50-60 Hz) (0-200/230 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED
15460 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (400/480 Vac, 50-60 Hz) (0-400/460 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED
16575 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (480/590 Vac, 50-60 Hz) (0-460/575 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED
6.0 THEORY6.1 DESCRIPTION OF AC MOTOR OPERATION ThreephaseACmotorsarecomprisedoftwomajorcomponents,thestatorandtherotor.Thestatoris
Ifthefrequencyappliedtothemotorisincreasedwhilethevoltageremainsconstant,torquecapabilitywilldecreaseasspeedincreases.Thiswill
“Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed.Also,the horsepower required varies with th
6.2.3 MICRO SERIES INPUTS AND OUTPUTS Thedrivehas two analog inputs (0-10 VDC and 4-20 mA) that can beused for speed reference, PI
The following describes the possible relay output settings: NONE This setting disables the relay output. RUN The relay energizes when the dri
7.0 INSTALLATION DRIVESMUSTNOTBEINSTALLEDWHERESUBJECTEDTO ADVERSE ENVI- RONMENTAL CONDITIONS! DRIVES MUST NOT BE INSTALLED WHERESUBJ
7.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE Severe damage to the drive can result if it is operated after a long period of storage or inactivity
8.0 INPUT AC REQUIREMENTS Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain
9.0 VOLTAGE SELECTION9.1 INPUT VOLTAGE RATINGS 115/230 Volt MICRO Seriesdrivesareratedfor240/120Vac,50-60Hzinput.Thedrivewillfunction
11.0 MICRO SERIES POWER WIRING DIAGRAM Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.
12.0 INITIAL POWER UP Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain cha
TABLE OF CONTENTS1.0 GENERAL ... 4 PRODUCT CHANGES ...
3. If the motor is rotating in the wrong direction, press the “STOP” key, remove power from the drive, wait three minutes for the
13.2 MICRO SERIES DISPLAY The following describes the possible display configurations for the SPEEDMASTER MICRO Series drive.13.2.1 MICRO SERIES DI
30 The following table shows the possible DRIVE STATUS indications that can appear on the drive display:DRIVE STATUS TABLE DISPLAY DESCRIPTION ST
13.2.2 MICRO SERIES DISPLAY IN RUN MODE WhenthedriveisintheRUNmode,thedefaultdisplaywilllooklikethis: AsintheSTOPmode,theENTER
3213.2.3 MICRO SERIES DISPLAY IN FAULT MODE When the drive trips on a fault, the display will automatically change to the FAULT display, which indic
33 Thetable belowshowsthe possibleSPEEDREFERENCESOURCEindications fortheauxiliarystatus display:SPEED REFERENCE TABLE DISPLAY DESCRI
14.0 CONTROL WIRING14.1 GENERAL14.1.1 KEYPAD CONTROL Thedrivecanbecontrolledbythekeypadorbycontroldeviceswiredtotheterminalstrip.T
14.2 START/STOP AND SPEED CONTROL14.2.1 REMOTE MODE SELECTION The REMOTE mode can be selected by one of two methods: 1. Program Parameter 30 - CO
14.2.3 ALTERNATE TWO-WIRE START/STOP CONTROL METHOD This method requires TB-13C to be set for RUN REVERSE, which will disable TB-1 a
14.2.4 THREE-WIRE START/STOP CONTROL A three-wire start/stop circuit can be accomplished by one of two methods on the MICRO Series drive. Follow the
TABLE OF CONTENTS (cont’d.)19.0 MICRO SERIES PID SET POINT CONTROL ... 77 FEEDBACK DEVICES . . . . . . . . . . . . . . . .
14.2.5 SPEED REFERENCE SIGNALS Thedriveallowsforthreeanalogspeedreferenceinputs:aspeedpotentiometer(10,000Ohm),0-10VDC,or 4-20 mA.
JOG TheJOGfunctiononlyworkswhenthedriveisinREMOTEmode,andonlywhenthedriveisinaSTOPcondition.TB-13Bcanbeprogrammedforeith
15.0 MICRO SERIES CONTROL WIRING DIAGRAMS15.1 MICRO SERIES TERMINAL STRIP Shown below is the terminal strip on the main control board, along with a
15.2 TWO-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained contact(s
15.3 THREE-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary contacts(
15.4 SPEED POT AND PRESET SPEED CONTROL ShownbelowisthewiringdiagramforacontrolschemethatutilizesaspeedpotandPRESETSPEEDSforspeed
16.0 PROGRAMMING THE MICRO SERIES DRIVE16.1 PROGRAMMING THE PARAMETERS The MICRO Series keypad serves two purposes: operating the drive w
Once the correct password is entered, the PROGRAM mode will be entered and the first parameter will be displayed, which is Parameter 0 - LINE VOLTS.
16.2 PARAMETER ACCESS USING SPEED DIAL SPEED DIAL is used to access parameters quickly using the parameter number. Once accessed, the
4717.0 PARAMETER MENUNOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE
3IMPORTANT NOTICEThe following , and information is supplied to you for your protection and to provi
48NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE3:IFLINEVOLTSIS
49PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT 43 @TB10A 0.00-360.0HZ(NOTE2) 60.00Hz 44 TB10B O
50PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT 65 PROGRAM MAINTAIN, RESET 60, RESET50(NOTE4) RES
5118.0 DESCRIPTION OF PARAMETERS 0 LINE VOLTS (LINEVOLTAGE) This parameter calibrates the drive for the correct input voltage, and can be set
1-4 SPEED #1-#4 (PRESETSPEEDS#1,#2,#3,AND#4) PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact clo
Example:Thecriticalfrequencyis21Hz,andabandwidthof2Hzisdesired.Therefore,setSKIP#1to20HzandsetSKIPBANDWIDTHto2Hz.Thisr
54 NOTE 1: 240/120 Vac units have the same limits as 240/200 Vac units. NOTE 2: The parameter value can be set below the minimum value shown, but th
11 MAX FRQ (MAXIMUMFREQUENCY) Thisparameterdefinestheupperlimitofthedrive’sspeedrange.MAXFRQisusedinconjunctionwithMINFRQ(Par
14 DYN BRAK (DYNAMICBRAKE) This parameter enables the dynamic braking circuit. Set this parameter to ON only if the optional dyna
The“speed-compensated”thermaloverloadcircuitoffersadditionalprotectionfromhighloadconditionsatlowspeeds,wheremotorcoolingisoften
1.0 GENERAL1.1 This manual covers the LEESON MICRO Series Inverters.1.2 PRODUCT CHANGES LEESON Electric reserves the right to discontinue or
18 BASE (BASEFREQUENCY) The BASE FREQUENCY determine the V/Hz ratio by setting the frequency at which the drive will output full
20 AC BOOST (ACBOOST) AC BOOST is similar to FX BOOST, but is only active when the drive is accelerating. During acceleration, theoutputvoltage
22 TORQUE (TORQUECURVESELECTION) ThisparameterisusedtoselectwhethertheoutputofthedrivefollowsaconstantorvariableV/Hzcurve.The
25 START (STARTMODE) Automaticstartofequipmentmayresultindamagetoequipmentand/orinjurytopersonnel!Automaticstartshouldonlybe
27 ROTATION (ROTATIONDIRECTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein
29 MANUAL (MANUAL) This parameter selects the speed reference source when the drive is set for MANUAL speed control (seeparameter28 - AUTO/MAN
33 SPEED DP (SPEEDDECIMALPOINT) This parameter is used to move the decimal point location in the speed display. This parameter will not have any
Example:SLEEP THRESHOLD isset to15Hz andSLEEP DELAYisset to60seconds. Ifthe drive operates below 15Hzfor60 seconds, the dr
41 AIN FLTR (ANALOGINPUTFILTER) Thisparameteradjuststhefilterontheanaloginputterminals(TB-5AandTB-5B)toreducetheeffectofanyel
47 TB13A (TB-13AINPUTFUNCTION) This parameter is used to select the function of terminal TB-13A. Closing TB-13A to TB-2 activates the TB-13
2.0 MICRO SERIES SPECIFICATIONS Storage Temperature -20° to 70° C Ambient Operating Temperature Chassis -10° to 55° C (With2.5and8kHZcar
49 TB13C (TB-13CINPUTFUNCTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein
50 TB13D (TB-13DFUNCTION) STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaults!The
SPEED #3 value. See Parameter 3 - SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS, ILIMIT CURRENTLIMIT-Therelayenergizeswhenthedrive
71 SPD=0HZ Therelayenergizeswhenthereisnooutputtothemotor,foranyreason,suchas:drive isinSTOPmode,driveisinRUNmode
NOTE 2: If a RESET command (Parameter 65 - PROGRAM) is issued through the serial link, this parameter will not default back to
65 PROGRAM (PROGRAMFACTORYDEFAULTS) STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaul
70 PID MODE (PIDMODESELECT) This parameter activates the PID function, and selects whether the PID control will be direct or reverse acting.
NOTE:Ifareverseactingfeedbackdeviceisbeingused,FB@MINshouldbesettothemaximumprocessvariable value, and FB @ MAX should be set to
relayoropen-collectoroutputwillde-energize,whichopensthestartcontactandstopsthedrive.WhenthesignalisequaltoorgreaterthantheMI
19.0 MICRO SERIES PID SET POINT CONTROL PID Set point Control allows the MICRO Series Control to maintain a process set point, such as PSI orCFM,w
64.0 MICRO SERIES DIMENSIONS4.1 TYPE 1 ENCLOSEDWRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ≤ 7
Forareverseactingtransducer,setParameter75-FB@MINtothemaximumprocessvariablefeedbackvalue,andsetParameter76-FB@MAXtothe
eachtype,sothesametypeofsignalcannotbeusedfortransducerfeedbackandsetpointreference.For example,a4-20mAsignalfromatransducer
When the drive is in PID mode, the DRIVE STATUS portion of the display will indicate actual output frequency(inHertz)insteadofRUN,andtherig
8120.0 TROUBLESHOOTING The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please con
82FAULT MESSAGES FAULT DESCRIPTION POSSIBLE CAUSES EXTERNAL Externalfault:TB-13Disopenorclosed ChecksettingofParameter to TB-2, depe
8321.0 USER SETTING RECORDPARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 0 LINE VOLTS AUTO 1
84PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 20 AC BOOST .0% 21 SLIP CMP .0% 22 TORQUE
8585PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 42 TB10A OUT NONE 43 @TB10A 60.00Hz 44
86PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 74 PID FB TB-5A 75 FB @ MIN 0.00% 76 FB
EC DECLARATION OF CONFORMITYWe,LEESON Electric1051 Cheyenne AvenueGrafton, Wisconsin 53024 U.S.A.declareundersoleresponsibilitythatthefollowing
7WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q
NOTES
A Regal BrandLEESON ElectricGrafton, Wisconsin 53024 U.S.A.PH: 262-377-8810FAX: 262-377-9025www.leeson.comREGAL BELOIT CANADAMississauga (Toronto), On