Leeson Micro Series Compact Inverters Manual de usuario Pagina 54

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 53
1-4 SPEED #1-#4 (PRESETSPEEDS#1,#2,#3,AND#4)
PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact closures
between terminal TB-2 and terminals TB-13A, TB-13B, and TB-13C. These terminals must be
programmed as preset speed selects using Parameters 47 - 49: TB13A, TB13B, and TB13C.
The preset speeds can only be set to values that are within the operating range defined by the minimum and
maximumfrequency(seeParameters:10-MINFREQ,and11-MAXFREQ).
The following table shows how each preset speed is selected using the TB-13 terminals. The terms OPEN
and CLOSED refer to the state of the TB-13 terminal relative to TB-2.
NOTE: SPEED #4 is selected if any two of the three TB-13 terminals are closed to TB-2
5,6 SKIP #1 & #2 (SKIPSPEED#1&#2)
7 BAND WID (SKIPBANDWIDTH)
These parameters are used to prevent the drive from operating continuously at critical speeds, or
frequencies, that cause excessive mechanical vibration of the driven equipment. The SKIP SPEEDS
(Parameters 5 and 6) and the SKIP BANDWIDTH (Parameter 7) are used to define up to two speed
avoidance ranges. The SKIP SPEED settings define the starting point of the speed range that is to be
avoided, and the SKIP BANDWIDTH setting defines how far the speed range extends beyond SKIP
SPEED.
52
PRESET SPEED ACTIVATION
SPEED # TB-13A TB13B TB-13C
1 CLOSED OPEN OPEN
2 OPEN CLOSED OPEN
3 OPEN OPEN CLOSED
4 CLOSED CLOSED OPEN
CLOSED OPEN CLOSED
OPEN CLOSED CLOSED
Vista de pagina 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 91 92

Comentarios a estos manuales

Sin comentarios