15.2 TWO-WIRE START/STOP CONTROL
Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained
contact(suchasthatfromaPLC)forRUNandSTOPcommands.ClosethecontacttoRUN,andopen
the contact to STOP. Also shown is the wiring for a 0-10 VDC or 4-20 mA speed reference signal.
NOTES:
1. Close TB-1 to TB-2 to RUN, and open to STOP.
2. IfREVERSEdirectionisrequired,ROTATIONmustbesettoFWD&REV,andTB-13Cmustbe
settoSTARTREVERSE(refertoParameters:27-ROTATION,and49-TB13C).
If REVERSE is not required, jumper TB-2 to TB-12A and eliminate the FWD/REV switch.
3. Program TB-13A, 13B, or 13C to select the appropriate speed reference signal that will control the
drivespeed(refertoParameters47,48,and49).WhenthatTB-13terminalisclosedtoTB-2,the
drive will respond to the selected speed reference signal. In the diagram above, TB-13A is programmed
to select either a 0-10 VDC or 4-20 mA signal.
4. If the contact closure is not made between TB-13A and TB-2 to select a speed reference, the drive will
default to MANUAL speed control, which is determined by Parameter 29 - MANUAL.
41