The following describes the possible relay output settings:
NONE This setting disables the relay output.
RUN The relay energizes when the drive is given a START command, and remains
energized until: a STOP command is given and the output frequency has
deceleratedto0.5Hz,thedrivehas“tripped”,ortheinputvoltageisremoved.
Note that this relay indicates only that the drive is in the RUN mode. It does not
necessarily indicate that the motor is turning.
FAULT The relay energizes when input voltage is applied to the drive and remains
energizeduntilthedrive“trips”intoafaultcondition,orinputvoltageisremoved.
/FAULT INVERSE FAULT - The relay energizes when the drive trips into a fault
condition,andremainsenergizeduntilthefaultconditioniscleared.
LOCK FAULT LOCKOUT - This relay is used when the drive is programmed to
automaticallyrestartafterafault.Therelayenergizeswheninputvoltageisapplied
tothedriveandremainsenergizeduntilthedrivehasfaultedandunsuccessfully
attempted five restarts, or input voltage is removed.
@SPEED AT SPEED - The relay energizes when the drive reaches the commanded
frequency.Toavoida“chattering”relay(constantlyenergizingandde-energizing),
due to small fluctuations in speed. the relay will change states only when the
actualspeedandthespeedsetpointdifferby3Hz.
ABOVE#3 The relay energizes when the output frequency of the drive exceeds the value
corresponding to the SPEED #3 value, and de-energizes when the output
frequencyreturnstoavaluelowerthantheSPEED#3value.SeeParameter3-
SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS.
ILIMIT CURRENT LIMIT - The relay energizes when the drive is operating in
currentlimit.Oncethecurrentlimitrelayisenergized,itremainsenergizedfor
a minimum of 500ms, regardless of whether the drive is still in current limit. At
theendofthe500msinterval,therelaywillde-energizeifthedriveisnolongerin
current limit. See Parameter 16 - CURRENT in Section 18.0 - DESCRIPTION
OF PARAMETERS.
AUT/MAN The relay energizes when the drive is in the AUTOMATIC mode, and
de-energizes in the MANUAL mode. Refer to Section 14.2.6 - SPEED
REFERENCE SELECTION.