Troubleshooting and Diagnostics
Status / Warning Cause Remedy
PdeC
PID Deceleration Status PID setpoint has nished
its ramp but the drive is still
decelerating to a stop.
PID
PID Mode Active Drive has been put into PID
Mode. See P200.
SLP
Sleep Mode is active See P240...P242
SP
Start Pending The drive has tripped into a
fault and will automatically
restart (P110 = 3...6)
To disable Auto-Restart, set
P110 = 0...2
spd
PID Mode disabled. Drive has been taken out of PID
Mode. See P200.
stoP
Output frequency = 0 Hz
(outputs U, V, W inhibited)
Stop has been commanded
from the keypad, terminal strip,
or network
Apply Start command (Start
Control source depends on
P100)