Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
P793
End Segment:
Digital Output
State
Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/
relay must be set to accept value the
from the sequencer: P140, P142=27
Bit1 TB14
P794
End Segment:
TB30 Analog
Output Value
0.00
0.00 {VDC} 10.00 TB30 conguration parameter must
be set to accept this value: P150
= 10
P795
End Segment:
Drive Action
0
0 Keep Running Recovery: Toggling the START
SEQUENCE will start the cycle
from ‘end segment Stop’ or ‘end
segment DC Brake’.
1 Stop (based on P111)
2 Coast to Stop
3 Quick Stop
4 Coast with DC Brake
5 Ramp with DC Brake
WARNING!
If P795 = 0 then toggling the start sequence input will also restart the
sequencer cycle but in the interim where TB13X is open the drive will
ramp to the standard or specied alternate speed source depending on
the drive conguration.
WARNING
If the input dened to “Start Sequence” is opened during a sequence, the
drive will exit sequencer mode and will run at the specied standard or
alternate speed source (dependent on drive conguration).